Why Room Integrity Testing Matters
A clean-agent fire suppression system must do more than discharge the correct quantity of extinguishing agent. The protected enclosure must retain the agent at or above the required minimum concentration for the specified hold time. Leakage through doors, cable penetrations, raised floors, ceilings, ducts, service openings and other pathways can allow the concentration to decay too quickly.
Room Integrity Testing - also called Enclosure Integrity Testing or a Door Fan Test - provides a non-destructive way to evaluate this performance without discharging the clean agent. A calibrated door-fan system is used to pressurize and depressurize the enclosure, establishing its leakage characteristics.
TEC Measurement + Salimus Engineering Software
Salimus has developed a web-based Integrity Test Calculator specifically to extend the normal TEC door-fan workflow into clean-agent enclosure hold-time analysis and reporting. The tool follows the door-fan method described in NFPA 2001 Annex Cand the equivalent ISO 14520-1 Annex E procedure.
The technician enters the site, technician, enclosure, agent and door-fan test information. The software then computes the leakage curve, Equivalent Leakage Area (EqLA),predicted agent hold time and PASS/FAIL result, while also performing quality checks and generating a professional PDF report.
Two Ways to Use TEC Test Data
The software supports the two field workflows most likely to be encountered:
· TECTITE Express / TECLOG result - enter the leakage exponent (n) and Flow Coefficient (C) already calculated for depressurization and pressurization. This is the recommended/default workflow.
· Raw fan-test points - enter measured pressure and airflow readings directly when a TECTITE/TECLOG result is not available. The Salimus application fits the leakage curve from the entered test points.
Optional cross-checks can include the correlation coefficient from a genuine multi-point test and the TECTITE Canadian EqLA at 10 Pa. The application can flag discrepancies that may indicate a units or data-entry problem.
Immediate Hold-Time Result
After the door-fan and enclosure information is entered, the result is presented immediately. In the demonstration shown in Figure 1, the application predicts ahold time of 913 seconds (15.22 minutes) against a required minimum of 600seconds (10 minutes), resulting in a clear PASS.
The same results area displays the Equivalent Leakage Area at 10 Pa, including depressurization, pressurization and combined values. This gives the technician a fast result while retaining the engineering data behind the decision.
More Than a PASS/FAIL Button
The Salimus application is designed to preserve engineering traceability rather than operate as a black-box calculator. It provides the leakage exponent, leakage coefficient, EqLA, mixture-density and column-pressure parameters, interface height and other calculation information used to review the predicted hold time.
The software also records project and test details, technician and equipment information, calibration certificate references, enclosure geometry, extinguishing-agent data, test techniques, engineering judgment, identified leakage locations and remediation notes.
Built-In Verification and QA Checks
Field testing can be affected by background pressure, damper movement, directional leakage behavior, insufficient pressure separation, unusual leakage exponents or simple data-entry errors. The Salimus application therefore performs automated checks and flags conditions that deserve review.
· Bias pressure during the fan test outside the applicable tolerance.
· Unusual leakage exponent values.
· Excessive disagreement between pressurization and depressurization results.
· Insufficient pressure separation in raw-point mode.
· Pressure mismatch between positive and negative test directions.
· Low correlation from a genuine multi-point test, when entered.
· Difference between calculated EqLA and an entered TECTITE Canadian EqLA cross-check.
· Missing witness or equipment calibration information.
· Predicted hold time below the required minimum.
These checks support the technician and reviewing engineer; they do not replace professional judgment.
One Click to a Professional PDF Report
Once the test has been reviewed, the technician can select Download PDF Report. The application automatically converts the project and test data into a structured Enclosure Integrity Test Report.
The generated report includes site and witness information, technician and calibrated equipment details, the PASS/FAIL result, predicted hold time, EqLA, finding sand recommendations, leakage test data, verification checks, the fan pressure-versus-flow curve, calculation breakdown, flags/anomalies and sign-off lines for the testing technician and witness.
Designed for Data Centres and Critical Enclosures
The workflow is particularly useful for data centres and other mission-critical facilities, where a project may contain many individually protected server, electrical, UPS, telecom and control rooms. A repeatable process for collecting data, checking test quality, calculating retention performance and producing consistent documentation can significantly simplify testing across multiple enclosures.
Software Included Free with Every Compatible TEC Fan Purchased from Salimus
TEC EQUIPMENT + SALIMUS SOFTWARE + SALIMUS TECHNICAL SUPPORT
Every compatible TEC fan system purchased from Salimus now includes access to the Salimus Integrity Test Calculator and PDF reporting application at no additional software charge.
This means the testing company receives not only the calibrated fan equipment needed to measure enclosure leakage, but also a purpose-built Salimus interface for converting those measurements into clean-agent hold-time calculations and professional reports - without a separate integrity-calculation software purchase.
A Complete Route from Measurement to Engineering Result
Salimus can support clients with TEC equipment supply, the Salimus Integrity Test Calculator, technician training, interpretation of results, and direct room-integrity and building-airtightness testing services.
TEC fan → measure → Salimus software → calculate & verify → PASS/FAIL → PDF report
If you need room integrity testing, TEC equipment, or want to establish your own enclosure-testing capability? Contact Salimus to discuss the appropriate TEC fan configuration, software access, training and technical support.